Weil McLain Boiler STAR 34 User Manual

GOLD G V  
W a t e r b o ile r — S e rie s 3  
Ve n t in g S u p p le m e n t  
S t a R-3 4  
S p e c ia l g a s ve n t s ys t e m ve n t a n d c o m b u s t io n  
a ir s u p p le m e n t  
Flex-L International, Inc. StaR-34 AL29-4C®  
Stainless Steel Special Gas Vent System may be  
used in new installations of GV-3 through GV-6  
boilers.  
Hazard definitions  
The following terms are used throughout this Venting Supplement to bring attention to the  
presence of hazards of various risk levels or to important information concerning the life of  
the product.  
Indicates presence of hazards that will cause severe personal injury, death  
or substantial property damage.  
Indicates presence of hazards that can cause severe personal injury, death  
or substantial property damage.  
Indicates presence of hazards that will or can cause minor personal injury  
or property damage.  
Indicates special instructions on installation, operation or maintenance  
that are important but not related to personal injury or property damage.  
To the installer:  
ThisVenting Supplement must only be used by a qualified installer/service  
technician. Read these instructions completely before beginning the  
installation. Failure to follow these instructions in proper order can cause  
severe personal injury, death or substantial property damage.  
To install a new vent system follow instructions in:  
This Venting Supplement.  
GV Boilers Vent/ Air Intake Termination Assembly Instructions, if  
using Weil-McLain Vent/Air Intake Termination Kit. — OR —  
GV Water Boiler Series 2 & 3 Direct vent Through-roof or Through-  
unused-chim ney Venting Supplem ent, if using Weil-McLain  
Through-Roof or Through-Unused-Chimney Termination Kit.  
StaR-34 manufacturers instructions supplied with vent material.  
For installations above 5,500 feet use only direct vent (ducted combustion  
air) when sidewall venting. All of the vertical (through-roof or through-  
unused-chimney) methods in thisVenting Supplement are acceptable. Can  
result in severe personal injury, death or substantial property damage if  
ignored.  
Part Number 550-110-268/0699  
 
S t a R-3 4 Ve n t in g S u p p le m e n t  
Vent termination  
anticipated snow line. In addition, vent termination must be  
at least 7 feet above public walkway and 3 feet above any forced  
air intake within 10 feet. Stay well away from trees, shrubs,  
and decorative items. Site conditions may dictate greater  
clearances. See Figure 1.  
Venting method definitions  
Direct vent — Uses outside combustion air with combustion  
air connector piping sealed at all joints and seams.Also known as  
“sealed combustion.  
Non-Direct vent — Uses inside combustion air with no  
9. Vent must terminate at least 4 feet horizontally, and in no  
case above or below, unless a 4 foot horizontal distance is  
maintained, from electric meters, gas meters,regulators, relief  
valves, and other equipment.  
10. Locate or guard vent to prevent condensate from damaging  
exterior finishes.  
11. Do not extend exposed vent pipe outside of building.  
Condensate could freeze and block vent pipe.  
12. Vent must terminate at least 6 feet away from adjacent walls.  
13. Do not terminate vent closer than 5 feet below roof overhang.  
combustion air connector piping.  
Properly locate vent termination  
Follow instructions on this page when  
determining vent location to avoid possibility  
of severe personal injury,death or substantial  
property damage.  
1. When using direct vent method — Refer to separate  
instructions packed with Weil-McLain direct vent termination  
kit and vent pipe manufacturer's instructions for additional  
locations.  
2. For location of non-direct vent vertical termination, see vent  
pipe manufacturer's instructions.  
3. Gases will form white plume in winter.Plume could obstruct  
window view.  
4. Prevailing winds could cause freezing of condensate and  
water/ice buildup on building, plants or roof.  
5. Locate or guard vent to prevent accidental contact by people  
or pets.  
6. Do not terminate vent in window well, stairwell, alcove,  
courtyard, or other recessed areas.  
7. Non-Direct vent installations only — Vent must terminate  
more than 1 foot below or to side of all doors or windows.  
See Figure 1.  
14. Do not terminate vent above any door or window.Condensate  
can freeze, causing ice formations.  
15. Do not use existing chimney as raceway if another appliance  
or fireplace is vented into or through chimney.  
16. Do not connect:  
Any other appliance to vent pipe.  
Multiple boilers to a common vent pipe.  
17. Do not wrap or insulate vent pipe and fittings.  
18. Canadian installations — See CAN/CGA B149.1 or B149.2  
Installation Code.  
19.  
A gas vent extending through an exterior  
wall shall not terminate adjacent to the wall  
or below building extensions such as eaves,  
parapets, balconies or decks. Failure to  
comply could result in severe personal  
injury, death or substantial property  
damage.  
8. Vent must terminate more than 1 foot above grade or  
Figure 1 Vent termination locations  
Forced  
air intake  
3 feet  
If within 10 feet  
1 foot  
7 feet  
1 ft  
26808  
Snow  
26807  
Part Number 550-110-268/0699  
3
 
G O LD G V W a t e r b o ile r — S e r ie s 3  
Installation  
Pre-installation planning  
1. Follow national, state, local or provincial codes or  
regulations when venting GV boiler.  
2. Choose vent method from those shown on page 5.  
3. Select vent run components from Table 2. Table 3  
states maximum vent run lengths and number of  
elbows.Do not exceed data in Table 3. Longer vent  
runs will slightly reduce boiler output. See Figure 2.  
4. If installing with direct vent method, use same  
maximum run length and number of elbows from  
step 2. Vent and combustion air connector piping  
configurations must match.Use suitable 3" material  
for combustion air connector piping, such as:  
Dryer vent  
Galvanized steel  
PVC (3" I.D.)  
5. Refer to vent termination WARNING, item 19 on  
page 3.  
Description  
Flex-L International, Inc.  
Part Number (Note 1)  
Table 2  
Parts list  
GV starter tee  
--  
GV termination coupling  
45o elbow  
SRAWGVT  
SRE4503  
90o elbow  
SRE9003  
6" pipe  
SR06P03  
1' pipe  
SR12P03  
2' pipe  
SR24P03  
3' pipe  
SR36P03  
5' pipe  
SR60P03  
Joiner band  
SRJB-14  
Weil-McLain Vent/Air Intake Termination Kit  
382-200-430 (Note 2)  
Weil-McLain Through-Roof or Through-Unused-Chimney Termination Kit 382-200-435 (Note 2)  
Notes  
1. Flex-L International, Inc. part number. Parts available through Flex-L International, Inc.  
2. Weil-McLain part number. Parts available through Weil-McLain distributor.  
Table 3  
Figure 2 Boiler output  
100  
Vent and combustion air connector piping  
lengths and number of elbows  
GV-3  
GV-4  
GV-5  
99  
98  
97  
96  
95  
Maximum vent  
length (feet)  
Total number of elbows  
0
2
3
4
5
6
7
8
GV-3 through GV-5 100 80 70 60 50 40 30 20  
GV-6 80 60 50 40 30 20 10 --  
GV-6  
0
20  
40  
60  
80  
100  
Total equivalent length (feet) of vent  
(from boiler to vent termination)  
4
Part Number 550-110-268/0699  
 
S t a R-3 4 Ve n t in g S u p p le m e n t  
For altitudes more than 5,500 feet above sea level — Do not use non-direct vent through  
sidewall methods as shown in Figures 4 and 6 below. Can cause severe personal injury, death  
or substantial property damage if ignored.  
Select  
vent  
method  
Figure 3 GV direct vent through sidewall  
Figure 4 GV non-direct vent through sidewall  
(using Weil-McLain Vent/Air Intake  
(using Weil-McLain Vent/Air Intake  
Termination Kit)  
Termination Kit) (See WARNING above.)  
Slope vent pipe downward, toward  
boiler, minimum ¼” per foot.  
Vent pipe  
Vent pipe  
ope  
Sl  
Sl  
Slope vent  
pipe  
ope  
Air pipe  
downward,  
toward boiler,  
minimum ¼”  
per foot.  
StaR-34  
StaR-34  
26801  
26802  
vent starter tee  
vent starter tee  
Figure 5 GV direct vent (using Weil-McLain  
Through-Roof or Through-Unused-  
Chimney Termination Kit)  
Figure 6 GV non-direct vent through sidewall  
(using termination coupling)  
(See WARNING above.)  
Slope vent pipe  
downward, toward  
boiler, minimum  
¼” per foot.  
StaR-34  
vent starter tee  
26804  
Slope vent pipe  
downward, toward  
boiler, minimum  
¼” per foot.  
Figure 7 GV non-direct vent through roof  
Slope vent pipe  
downward,  
toward boiler,  
minimum ¼”  
per foot.  
StaR-34  
vent starter tee  
StaR-34  
vent starter tee  
26805  
26803  
Part Number 550-110-268/0699  
5
 
G O LD G V W a t e r b o ile r — S e r ie s 3  
Installation — assembly  
Connect vent starter  
tee to boiler  
Follow the instructions in the GV Series 3 Boiler Manual section IIb to connect the vent  
starter tee to the boiler.  
Follow vent pipe manufacturer's instructions for sealing the vent.Vent and  
combustion air connector piping must be sealed gas-tight to prevent  
possibility of flue gas spillage and carbon monoxide emissions, resulting in  
severe personal injury or death.  
Construct vent and  
optional  
combustion air run  
1. Follow StaR-34 manufacturer's instructions to construct vent run and for methods of  
supporting vent runs.  
Clean joints before sealing. See vent pipe manufacturer's instructions to clean joints.  
Use their specified sealant (maximum 250 0F flue temperature). Do not use screws.  
Do not mix types or manufacturers of vent materials.  
Maintain minimum one-inch clearance from combustible materials to vent pipe; 0"  
clearance for noncombustible materials.  
Install vent pipe with seams on top of vent runs.  
If needed, male end of vent pipe may be cut to provide correct length. See vent pipe  
manufacturer's instructions for use.  
2. If installing with direct vent method, use instructions provided with Weil-McLain  
termination kit. See Figures 3, 4 or 5 on page 5.  
Ve n t in g t h ro u g h s id e w a ll  
Connect vent run to  
termination  
1. If using Weil-McLain Vent/Air Intake Termination Kit, see instructions provided in that  
kit. Applies to direct (Figure 3, page 5) or non-direct vent (Figure 4, page 5) method.  
2. If using non-direct method with termination coupling only, see Figures 8 and 9.  
If passing through noncombustible wall, provide hole diameter large enough to insert  
the pipe through. Sleeve and spacers are not required.  
3. Maintain minimum one-inch clearance from combustible materials to vent pipe; 0"  
clearance for noncombustible materials.  
4. Refer to vent termination WARNING, item 19 on page 3.  
Ve n t in g t h ro u g h e xis t in g c h im n e y o r ro o f  
1. Direct vent method — follow instructions supplied in Weil-McLain Through-Roof or  
Through-Unused-Chimney Termination Kit to assemble termination.  
2. Non-Direct vent method (only through the roof, not through chimney):  
Vent pipe must extend through roof flashing, jacket or thimble. See Figure 10.  
Vent may pass through floor, inside wall or concealed space when installed according  
to vent pipe manufacturer's instructions.  
3. Maintain minimum one-inch clearance from combustible materials to vent pipe.  
6
Part Number 550-110-268/0699  
 
S t a R-3 4 Ve n t in g S u p p le m e n t  
Figure 8 Sidewall termination installation (non-direct venting)  
¼" to ¾" between stop  
on termination and  
metal plate  
4" galvanized sleeve  
(through 4¹⁄₈" hole for  
combustible wall)  
Pipe section  
Metal plate  
Metal plate  
Spacers (2)  
(to support and  
center vent in  
sleeve)  
Pipe section  
Sealant  
Sealant  
Termination coupling  
26809  
Figure 9 Non-direct vent through sidewall (using  
Figure 10 Non-Direct vent through roof  
Follow StaR-34 manufacturers instructions  
for proper installation of vent runs, including  
slope and support.  
termination coupling)  
Follow StaR-34 manufacturers instructions  
for proper installation of vent runs, including  
slope and support.  
StaR-34  
vent starter tee  
StaR-34  
vent starter tee  
26805b  
26804b  
Part Number 550-110-268/0699  
7
 
G O LD G V W a t e r b o ile r — S e r ie s 3  
Installation — assembly continued  
Finish the vent  
installation  
In s t a llin g c o n d e n s a t e t u b in g  
Figure 11  
1. See Figure 11 to install condensate tubing  
(provided by others). Use condensate pump  
if floor drain is higher than condensate drain  
on boiler.  
Installation of condensate tubing  
StaR-34  
vent starter tee  
If required:  
use a low-profile pump — OR —  
set boiler on foundation (see GV Series  
3 Boiler Manual) to allow gravity flow  
to pump.  
2. Size pump in gal/hr. (boiler model):  
0.78 (GV-3)  
1.17 (GV-4)  
1.56 (GV-5)  
1.95 (GV-6)  
5/8" O.D. tubing,  
provided by  
others  
26806  
Refer to pump manufacturer's instructions.  
Drain to a non-freezing area.  
If ve n t p ip e o r c o m b u s t io n a ir p ip e m u s t b e re a s s e m b le d  
When vent pipe or combustion air pipe is disconnected for any reason, it must be reassembled  
and resealed according to thisVenting Supplement,the direct vent termination kit instructions  
and the vent pipe manufacturer's instructions.  
Sealant recommended by vent pipe manufacturer must be used as indicated  
in their instructions. Vent and combustion air connector piping must be  
sealed gas-tight to prevent possibility of flue gas spillage and carbon  
monoxide emissions, resulting in severe personal injury or death.  
Weil-McLain  
500 Blaine Street  
Michigan City, IN 46360-2388  
8
Part Number 550-110-268/0699  
 

Whirlpool Range 9782474A User Manual
White Sewing Machine W1750C User Manual
Wolfgang Puck Food Processor BFPR0040 User Manual
Wolfgang Puck Fryer BDFR0040 User Manual
Woods Equipment Compact Loader 211822 User Manual
Zanussi Cooktop ZCGHL50 User Manual
Zanussi Dishwasher ZSF 6150 S User Manual
Zanussi Freezer ZO 25 N User Manual
Zanussi Refrigerator Z1163TR User Manual
Zhone Technologies Network Card zPON User Manual